Pump head calculator

Enter each pipe segment's size, flow, length and fittings, add static head, equipment losses and a margin, and get the pump total head and shaft power. Straight-pipe loss uses the same Darcy-Weisbach solver as the pipe sizing calculator.

Basis

Each segment adds straight, fitting and equivalent-length losses; static head and equipment losses are added and the margin is applied to give total head. The pump flow is taken as the largest segment flow.

ItemEquationNotes · basis
Straight pipeΔp_L = R · L, R = (f / D) · ρV²/2f from Colebrook (64/Re if laminar). Roughness is the pipe type's default (steel 0.046 mm, copper 0.0015 mm). Same function as the pipe sizing calculator
Fittings and valvesΔp_K = K · ρV²/2, K = f_T · Σ n·(L/D)Crane TP-410 method. n is the count, L/D from the table below
Fully turbulent friction factorf_T = [−2 log₁₀(ε_T / (3.7 D))]⁻², ε_T = 0.046 mmCrane defines f_T as the fully turbulent value for clean commercial steel; copper and stainless use it too (50A SGP: 0.0190). Values from this formula can differ from the f_T in Crane's table by up to about 4 % depending on size (e.g. 4 in: table 0.017, formula 0.0163)
Equivalent lengthΔp_E = R · L_eFor strainers and special valves not in the table, enter the maker's equivalent length in m
Total headH = (H_s + Σ Δp / (ρ g) + H_e) × (1 + m)H_s static head (negative if the discharge level is lower), H_e equipment head (kPa divided by ρ g), m the margin. This calculator applies the margin to the whole sum; some practice applies it to friction losses only. If H is 0 or less, the result says no pump is needed
Water and shaft powerP_w = ρ g Q H, P_s = P_w / ηQ in m³/s, H in m, η the pump efficiency at the duty point

Fitting L/D values

Only values checked in the Crane TP-410 appendix are listed. K is shown for 50A SGP pipe (f_T 0.0190). Enter other fittings in the equivalent-length field.

FittingL/DK (50A SGP)
90° elbow300.57
Tee, run200.38
Tee, branch601.14
Gate valve80.15
Swing check valve1001.90

Worked example

Water at 20 °C (ρ = 998.21 kg/m³), SGP steel. Segment 1: 80A (bore 80.7 mm), 600 L/min, 50 m straight, 6 elbows, 2 tees on the run, 2 gate valves, 1 swing check. V = 1.955 m/s, f = 0.01960, R = 463.3 Pa/m, so the straight loss is 23.16 kPa. Σ L/D = 6×30 + 2×20 + 2×8 + 100 = 336, f_T = 0.01720, K = 5.780 and ρV²/2 = 1,907.7 Pa give 11.03 kPa for fittings. Total 34.19 kPa = 3.493 m.

Segment 2: 65A (bore 67.9 mm), 300 L/min, 30 m straight, 4 elbows, 1 tee branch, 1 gate valve and a strainer of 3 m equivalent length. V = 1.381 m/s, R = 297.0 Pa/m: straight 8.91 kPa, Σ L/D = 188, f_T = 0.01790, K = 3.365 give 3.20 kPa for fittings, and 0.89 kPa for the strainer. Total 13.00 kPa = 1.328 m.

Static head 15 m, chiller evaporator 50 kPa = 5.108 m. Subtotal 15 + 4.821 + 5.108 = 24.93 m; with a 10 % margin the total head is 27.42 m (268.4 kPa). Water power = 998.21 × 9.80665 × 0.01 × 27.42 = 2.68 kW; at 60 % efficiency the shaft power is 4.47 kW.

Limits

Check pump selection and the performance curve (duty point, efficiency, NPSH) against the maker's data. This calculator sums one path in series; it does not balance flows between parallel branches or include control-valve drops.

L/D values are representative; actual fittings and valves vary with maker and size. If you have maker's data, use the equivalent-length field.