Wet bulb and relative humidity calculator

Enter a measured dry bulb with RH, wet bulb or dew point and get every other humidity value (RH, wet bulb, dew point, absolute humidity, vapor pressure, specific volume, enthalpy) with the same equations as the chart calculator.

Definitions

Relative humidity RH (%)
Ratio of the actual vapor pressure to the saturation vapor pressure at the same temperature. With the same moisture, it falls as air warms and rises as it cools.
Absolute humidity (g/kg dry air · g/m³)
HVAC uses the humidity ratio, grams of vapor per kg of dry air; meteorology uses vapor density, grams of vapor per m³ of air. The humidity ratio does not change with temperature alone.
Wet bulb temperature (°C)
The temperature a thermometer wrapped in wet wick settles at as water evaporates. The drier the air, the larger the gap to the dry bulb; at saturation they are equal.
Dew point (°C)
The temperature at which condensation starts when the air is cooled at constant moisture. It depends only on the vapor pressure, so it carries the same information as the humidity ratio.

Psychrometer RH table (101.325 kPa)

Rows are dry bulb, columns the dry bulb minus wet bulb depression (K), cells the relative humidity (%). Computed with the same engine at standard pressure (ventilated psychrometer basis; unventilated screen tables differ slightly). A dash means the combination cannot exist.

Dry bulb / depression °C1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K
1088776655443425156-
1590807162534436282013
2091837467595244383125
2592857770635751453933
3093867973676155504540
3593878175706459544945
4094888277726762575349

Saturation vapor pressure by temperature

Saturation vapor pressure from the Hyland-Wexler equations (ASHRAE 2017 chapter 1) and the saturated vapor density, the most water vapor one m³ of air can hold at 100 % RH. Values below 0 °C are over ice.

Temperature °CSaturation pressure kPaSaturated vapor density g/m³
−100.25992.14
−50.40183.25
00.61124.85
50.87256.80
101.22809.40
151.705412.82
202.338817.29
253.169223.03
304.246030.35
355.627839.57
407.383551.09
459.593265.34
5012.349982.81

Frequently asked questions

What is the difference between relative and absolute humidity?

Relative humidity is the share (%) of the most vapor the air can hold at that temperature; absolute humidity is the actual amount (g/kg or g/m³). Cool 25 °C, 50 % air to 15 °C and the humidity ratio stays 9.88 g/kg while RH rises to about 93 %.

How is wet bulb temperature measured and calculated?

Wrap a thermometer in a wet wick, blow about 2~5 m/s of air over it (aspirated psychrometer) and read it once it settles. The calculator gets the humidity ratio from the ASHRAE wet bulb equation and then RH. Example: 30 °C dry bulb and 25 °C wet bulb is about 67 % RH.

How is the discomfort index calculated?

Put dry bulb t (°C) and RH (%) into the Korea Meteorological Administration formula DI = 0.81 t + 0.01 RH (0.99 t − 14.3) + 46.3. For 30 °C and 70 %, DI ≈ 81.4. See the KMA guidance for its comfort bands.

Equations and sources

Sources

Last updated 2026-11-09.