Cooling tower calculator: range, approach, make-up water
Enter the circulating flow, inlet and outlet water temperatures and outdoor wet bulb to get range, approach, efficiency, heat rejection (cooling tons) and evaporation, blowdown and make-up water at once.
Terms and principles
- Range and approach
- Range is how much the tower cools the water (inlet − outlet), and approach is how close the outlet gets to the outdoor wet bulb (outlet − wet bulb). Efficiency = range / (inlet − wet bulb), 100 % if the water reached the wet bulb.
- Cooling ton (CRT)
- 1 cooling ton = 3,900 kcal/h ≈ 4.536 kW: cooling 13 L/min of water from 37 °C to 32 °C at a 27 °C wet bulb (13 × 60 × 5 = 3,900 kcal/h), used in Korea and Japan. The US cooling ton is 15,000 Btu/h, a different value.
- Evaporation
- The tower evaporates part of the water and its latent heat cools the rest. If all heat left by evaporation, E = Q / hfg, about 0.87 % of the flow at a 5 K range. In practice some heat goes to the air as sensible heat, so the rule of thumb (0.00085 × 1.8 × flow × range) is a little lower.
- Cycles, blowdown and make-up
- Evaporated water is pure, so salts and hardness build up in the rest. How many times the make-up concentration you allow is the cycles of concentration (COC); the water bled off to hold it is the blowdown B = E / (COC − 1) − D. Make-up is M = E + D + B.
Flow and make-up water by cooling tons (37 → 32 °C, wet bulb 27 °C)
Standard condition with cycles of concentration 4 and 0.1 % drift, computed at build time with the same engine as the calculator above. Daily make-up assumes 24 h operation.
| Cooling tons CRT | Circulating water flow L/min | Heat rejection kW | Evaporation (E) m³/h | Blowdown (B) m³/h | Make-up water (M) m³/h | Make-up per day m³ |
|---|---|---|---|---|---|---|
| 1 | 13 | 4.54 | 0.00675 | 0.00147 | 0.00900 | 0.216 |
| 5 | 65 | 22.68 | 0.0337 | 0.00735 | 0.0450 | 1.08 |
| 10 | 130 | 45.36 | 0.0675 | 0.0147 | 0.0900 | 2.16 |
| 30 | 390 | 136.1 | 0.202 | 0.0441 | 0.270 | 6.48 |
| 50 | 650 | 226.8 | 0.337 | 0.0735 | 0.450 | 10.8 |
| 100 | 1,300 | 453.6 | 0.675 | 0.147 | 0.900 | 21.6 |
| 200 | 2,600 | 907.1 | 1.35 | 0.294 | 1.80 | 43.2 |
| 300 | 3,900 | 1,360.7 | 2.02 | 0.441 | 2.70 | 64.8 |
| 500 | 6,500 | 2,267.8 | 3.37 | 0.735 | 4.50 | 108 |
| 1,000 | 13,000 | 4,535.7 | 6.75 | 1.47 | 9.00 | 216 |
Frequently asked questions
How do you calculate cooling tons?
Compute heat rejection Q = flow × specific heat × range in kcal/h and divide by 3,900. 13 L/min from 37 to 32 °C gives 13 × 60 × 1 × 5 = 3,900 kcal/h = 1 cooling ton (about 4.536 kW). 100 cooling tons need 1,300 L/min (78 m³/h).
What is the difference between range and approach?
Range is the water temperature drop (inlet − outlet); approach is the gap between outlet water and outdoor wet bulb. The load and flow set the range; the tower size sets the approach. A smaller approach needs a much bigger tower, so 3 to 6 K is typical (5 K in the Korean standard).
How much make-up water does a cooling tower need?
Make-up M = evaporation E + drift D + blowdown B. At the standard condition (5 K range) evaporation is about 0.87 % of the flow; with 4 cycles the blowdown is a third of evaporation minus drift, so make-up is about 1.15 % of the flow. 100 cooling tons take about 0.9 m³ per hour, 22 m³ per day.
How do cooling tons differ from refrigeration tons?
Refrigeration tons (1 USRT = 3,024 kcal/h, 1 JRT = 3,320 kcal/h) are the heat a chiller removes from chilled water; cooling tons (1 CRT = 3,900 kcal/h) are the heat the tower rejects to air. The tower also rejects compressor heat, so practice takes cooling tons ≈ 1.3 × refrigeration tons. This calculator does not use that ratio; it works from flow and water temperatures.
Equations and sources
- Range R = t1 − t2, approach A = t2 − twb, efficiency η = R / (t1 − twb) × 100 %
- Heat rejection Q = ṁ cp R (ṁ = ρ Qw, ρ = 1,000 kg/m³, cp = 4.1868 kJ/(kg·K)), cooling tons = Q [kcal/h] / 3,900
- Evaporation E = Q / hfg (hfg from the steam table at the mean water temperature), rule of thumb E ≈ 0.00085 × 1.8 × Qw × R
- Drift D = Qw × drift rate, blowdown B = E / (COC − 1) − D, make-up M = E + D + B
Sources
- Cooling ton 1 CRT = 3,900 kcal/h: 13 L/min at the JIS standard condition (37 → 32 °C, wet bulb 27 °C), as used in Korean HVAC textbooks and tower catalogues
- Latent heat hfg: IAPWS-IF97 (same as the steam table tool); dry bulb and RH to wet bulb: ASHRAE Handbook Fundamentals 2017, chapter 1
- Evaporation rule: the water-treatment rule E = 0.00085 × flow × ΔT(°F) (0.085 % of flow per °F), × 1.8 for °C
- ASHRAE Handbook HVAC Systems and Equipment, Cooling Towers chapter: evaporation, drift and blowdown balance