Cooling tower calculator: range, approach, make-up water

Enter the circulating flow, inlet and outlet water temperatures and outdoor wet bulb to get range, approach, efficiency, heat rejection (cooling tons) and evaporation, blowdown and make-up water at once.

Terms and principles

Range and approach
Range is how much the tower cools the water (inlet − outlet), and approach is how close the outlet gets to the outdoor wet bulb (outlet − wet bulb). Efficiency = range / (inlet − wet bulb), 100 % if the water reached the wet bulb.
Cooling ton (CRT)
1 cooling ton = 3,900 kcal/h ≈ 4.536 kW: cooling 13 L/min of water from 37 °C to 32 °C at a 27 °C wet bulb (13 × 60 × 5 = 3,900 kcal/h), used in Korea and Japan. The US cooling ton is 15,000 Btu/h, a different value.
Evaporation
The tower evaporates part of the water and its latent heat cools the rest. If all heat left by evaporation, E = Q / hfg, about 0.87 % of the flow at a 5 K range. In practice some heat goes to the air as sensible heat, so the rule of thumb (0.00085 × 1.8 × flow × range) is a little lower.
Cycles, blowdown and make-up
Evaporated water is pure, so salts and hardness build up in the rest. How many times the make-up concentration you allow is the cycles of concentration (COC); the water bled off to hold it is the blowdown B = E / (COC − 1) − D. Make-up is M = E + D + B.

Flow and make-up water by cooling tons (37 → 32 °C, wet bulb 27 °C)

Standard condition with cycles of concentration 4 and 0.1 % drift, computed at build time with the same engine as the calculator above. Daily make-up assumes 24 h operation.

Cooling tons CRTCirculating water flow L/minHeat rejection kWEvaporation (E) m³/hBlowdown (B) m³/hMake-up water (M) m³/hMake-up per day m³
1134.540.006750.001470.009000.216
56522.680.03370.007350.04501.08
1013045.360.06750.01470.09002.16
30390136.10.2020.04410.2706.48
50650226.80.3370.07350.45010.8
1001,300453.60.6750.1470.90021.6
2002,600907.11.350.2941.8043.2
3003,9001,360.72.020.4412.7064.8
5006,5002,267.83.370.7354.50108
1,00013,0004,535.76.751.479.00216

Frequently asked questions

How do you calculate cooling tons?

Compute heat rejection Q = flow × specific heat × range in kcal/h and divide by 3,900. 13 L/min from 37 to 32 °C gives 13 × 60 × 1 × 5 = 3,900 kcal/h = 1 cooling ton (about 4.536 kW). 100 cooling tons need 1,300 L/min (78 m³/h).

What is the difference between range and approach?

Range is the water temperature drop (inlet − outlet); approach is the gap between outlet water and outdoor wet bulb. The load and flow set the range; the tower size sets the approach. A smaller approach needs a much bigger tower, so 3 to 6 K is typical (5 K in the Korean standard).

How much make-up water does a cooling tower need?

Make-up M = evaporation E + drift D + blowdown B. At the standard condition (5 K range) evaporation is about 0.87 % of the flow; with 4 cycles the blowdown is a third of evaporation minus drift, so make-up is about 1.15 % of the flow. 100 cooling tons take about 0.9 m³ per hour, 22 m³ per day.

How do cooling tons differ from refrigeration tons?

Refrigeration tons (1 USRT = 3,024 kcal/h, 1 JRT = 3,320 kcal/h) are the heat a chiller removes from chilled water; cooling tons (1 CRT = 3,900 kcal/h) are the heat the tower rejects to air. The tower also rejects compressor heat, so practice takes cooling tons ≈ 1.3 × refrigeration tons. This calculator does not use that ratio; it works from flow and water temperatures.

Equations and sources