Humidifier sizing calculator · Humidification load kg/h
Enter the target room dry bulb and RH, the air state before humidifying and the airflow to get the humidification load in kg/h from the humidity ratio difference and dry-air mass flow, plus humidifier capacity with margin, steam humidifier power and the target dew point.
Terms and principles
- Humidification load
- The water vapour to add, L = ṁa (x2 − x1) kg/h. ṁa is the dry-air mass flow (airflow ÷ specific volume) and x is kg of vapour per kg of dry air (humidity ratio). Textbooks shorten ṁa to about 1.2 × airflow.
- Why heated air feels dry
- Winter outdoor air at 0 °C and 50 % holds about 1.88 g/kg. Heating it to 22 °C keeps the humidity ratio, so RH drops to about 12 %. The humidity ratio before humidifying therefore follows the outdoor state, and you add the difference up to 22 °C, 40 % (about 6.56 g/kg).
- Humidifier capacity and power
- Humidifier capacity is the calculated load times the margin. A steam (electrode or resistive) humidifier needs about 2,633 kJ to heat and boil 1 kg of water, about 0.73 kW per kg/h. Evaporative and ultrasonic types use far less power but cool the air.
Humidification per 1,000 CMH (room 22 °C)
Humidification load in kg/h for a 22 °C room by target RH (rows) and humidity ratio before x1 (columns). 1,000 CMH is the volume of air heated to 22 °C at standard pressure, computed at build time with the same engine as the calculator above. Winter outdoor 0 °C, 50 % is about 1.9 g/kg; −10 °C, 50 % is about 0.8 g/kg.
| Target RH \ x1 | 1.0 g/kg | 1.5 g/kg | 2.0 g/kg | 2.5 g/kg | 3.0 g/kg | 4.0 g/kg |
|---|---|---|---|---|---|---|
| 30 % | 4.67 | 4.07 | 3.47 | 2.87 | 2.27 | 1.08 |
| 40 % | 6.64 | 6.04 | 5.44 | 4.84 | 4.24 | 3.04 |
| 50 % | 8.63 | 8.02 | 7.42 | 6.82 | 6.22 | 5.02 |
Frequently asked questions
How do you calculate the humidification load?
L = ṁa × (x2 − x1). For a 22 °C, 40 % room (x2 ≈ 6.56 g/kg) and 10,000 CMH of supply air made from 0 °C, 50 % outdoor air heated to 22 °C (x1 ≈ 1.88 g/kg), ṁa = 10,000 / 0.839 ≈ 11,924 kg/h and L ≈ 11,924 × 0.00468 ≈ 55.8 kg/h. The textbook 1.2 × 10,000 × 0.00468 ≈ 56.2 kg/h agrees within 1 %.
Should I enter the supply airflow or the outdoor airflow?
Both use the same equation; only the meaning of x1 changes. "Total supply air" is when all the air through the humidifier goes from x1 to the target x2 (100 % outdoor air units or humidifying after mixing). "Outdoor air intake" treats return air as already at room humidity and counts only raising the outdoor air to room humidity. Internal moisture gains reduce it.
Will humidifying cause condensation?
Yes, on any surface colder than the target dew point. At 22 °C, 40 % the dew point is about 7.8 °C, so poorly insulated window glass can be colder than that when it is freezing outside. Lower the target RH or check surface temperatures with the dew point calculator.
Equations and sources
- Humidification load L = ṁa (x2 − x1) kg/h, dry-air mass flow ṁa = Q / v (v: specific volume at the airflow state, m³/kg(DA))
- Textbook L′ = 1.2 × Q × (x2 − x1) (air density fixed at 1.2 kg/m³), humidifier capacity Lcap = L × (1 + margin)
- Steam humidifier power P ≈ Lcap × (4.1868 × (100 − 10) + hfg(100 °C)) / 3,600 kW, hfg ≈ 2,256 kJ/kg, efficiency 1 (approximate)
Sources
- Humidity ratio, specific volume and dew point: ASHRAE Handbook Fundamentals 2017 (SI), chapter 1 psychrometrics; same engine as the psychrometric calculator
- Latent heat hfg at 100 °C: IAPWS-IF97 (same as the saturated steam table tool). The ρ = 1.2 kg/m³ shortcut follows common HVAC textbooks
Last updated 2026-11-23.