Heat exchanger calculator: LMTD, heat duty and area
Enter hot and cold inlet and outlet temperatures and one flow to get the heat duty, the other flow (or an outlet temperature), terminal differences and LMTD, effectiveness and, with U, the required area.
Terms and principles
- Log mean temperature difference (LMTD)
- Inside a heat exchanger the difference between the two fluids changes exponentially from one end to the other. The proper mean is LMTD = (ΔT1 − ΔT2) / ln(ΔT1/ΔT2), used as the driving difference in Q = U · A · LMTD. If ΔT1 = ΔT2, LMTD equals that value.
- Counterflow and parallel flow
- In counterflow the fluids run in opposite directions, in parallel flow the same way. Terminal differences are ΔT1 = Th1 − Tc2, ΔT2 = Th2 − Tc1 for counterflow and ΔT1 = Th1 − Tc1, ΔT2 = Th2 − Tc2 for parallel flow. For the same temperatures counterflow has the larger LMTD, so less area, and it can heat the cold side above the hot outlet.
- Overall heat transfer coefficient U
- The combined conductance of both films, the wall and fouling, in W/(m²·K). Water to water plate units are roughly 3,000~6,000 and shell and tube about 800~1,500; the real value depends on velocity and plate pattern, so take it from the manufacturer.
- Effectiveness ε
- The actual duty divided by the theoretical maximum Qmax = Cmin (Th1 − Tc1). It shows how close the temperature change of the side with the smaller C = ṁ cp comes to the inlet-to-inlet difference.
LMTD table by ΔT1 and ΔT2
LMTD (K) for terminal differences ΔT1 (rows) and ΔT2 (columns). The formula is the same for any flow arrangement; values were computed at build time with the same engine as the calculator above. The diagonal is ΔT1 = ΔT2, equal to that value.
| ΔT1 \ ΔT2 | 2 K | 5 K | 10 K | 15 K | 20 K | 30 K | 40 K | 60 K |
|---|---|---|---|---|---|---|---|---|
| 2 K | 2.00 | 3.27 | 4.97 | 6.45 | 7.82 | 10.34 | 12.68 | 17.05 |
| 5 K | 3.27 | 5.00 | 7.21 | 9.10 | 10.82 | 13.95 | 16.83 | 22.13 |
| 10 K | 4.97 | 7.21 | 10.00 | 12.33 | 14.43 | 18.20 | 21.64 | 27.91 |
| 15 K | 6.45 | 9.10 | 12.33 | 15.00 | 17.38 | 21.64 | 25.49 | 32.46 |
| 20 K | 7.82 | 10.82 | 14.43 | 17.38 | 20.00 | 24.66 | 28.85 | 36.41 |
| 30 K | 10.34 | 13.95 | 18.20 | 21.64 | 24.66 | 30.00 | 34.76 | 43.28 |
| 40 K | 12.68 | 16.83 | 21.64 | 25.49 | 28.85 | 34.76 | 40.00 | 49.33 |
| 60 K | 17.05 | 22.13 | 27.91 | 32.46 | 36.41 | 43.28 | 49.33 | 60.00 |
Frequently asked questions
How do you calculate LMTD?
Find the two terminal differences and use LMTD = (ΔT1 − ΔT2) / ln(ΔT1/ΔT2). In counterflow with the hot side 80 → 50 °C and the cold side 20 → 40 °C, ΔT1 = 80 − 40 = 40 K, ΔT2 = 50 − 20 = 30 K and LMTD = 10 / ln(40/30) ≈ 34.76 K, a little below the 35 K arithmetic mean.
How do counterflow and parallel flow differ?
With the same temperatures in parallel flow, ΔT1 = 80 − 20 = 60 K, ΔT2 = 50 − 40 = 10 K and LMTD = 50 / ln 6 ≈ 27.91 K. That is about 20 % below counterflow (34.76 K), so the same duty needs about 25 % more area. In parallel flow the cold outlet can never rise above the hot outlet.
How do you find the other side's flow?
Use the energy balance ṁh cph (Th1 − Th2) = ṁc cpc (Tc2 − Tc1). If 100 L/min of hot water cools from 80 to 50 °C, Q = 100/60 × 4.1868 × 30 ≈ 209.3 kW; to warm the cold side from 20 to 40 °C it needs 209.3 / (4.1868 × 20) = 2.5 kg/s, that is 150 L/min.
How do you find the required heat transfer area?
A = Q / (U · LMTD). In the example above (Q ≈ 209.3 kW, LMTD 34.76 K) a plate unit with U = 4,000 W/(m²·K) needs A = 209,340 / (4,000 × 34.76) ≈ 1.51 m². U varies a lot with velocity, plate pattern and fouling, so use the manufacturer's value and add the fouling margin separately.
Equations and sources
- Heat balance Q = ṁh cph (Th1 − Th2) = ṁc cpc (Tc2 − Tc1)
- Counterflow ΔT1 = Th1 − Tc2, ΔT2 = Th2 − Tc1; parallel flow ΔT1 = Th1 − Tc1, ΔT2 = Th2 − Tc2
- LMTD = (ΔT1 − ΔT2) / ln(ΔT1/ΔT2); if ΔT1 = ΔT2, LMTD = ΔT1
- Area A = Q / (U · LMTD), effectiveness ε = Q / (Cmin (Th1 − Tc1)), C = ṁ cp
Sources
- LMTD, effectiveness and area: F. P. Incropera et al., Fundamentals of Heat and Mass Transfer, chapter 11 (heat exchangers)
- Water cp = 4.1868 kJ/(kg·K) = 1 kcal/(kg·°C) and 1 kg/L for volume flow: Korean HVAC exam textbook practice (same basis as the cooling tower calculator)
- Glycol 30 % specific heat: rough values near the ASHRAE Handbook Fundamentals chapter 31 (secondary coolants) tables. The U ranges are general engineering figures; actual selection follows manufacturer data