Dew point calculator and condensation check
Get the dew point from room temperature and relative humidity. Add the surface temperature of a window, wall or chilled-water pipe to see whether condensation forms and how far to lower the humidity to stop it. Below, choose the insulation material and thickness to check surface condensation on insulated pipe and get the minimum thickness that prevents it.
What the dew point is
Air can hold only so much water vapor; when it cools, the extra comes out as droplets. The temperature where that starts is the dew point. At the same temperature, more humid air has a higher dew point.
Below 0 °C the vapor turns to ice (frost) instead of water, so it is called the frost point and is computed with the saturation pressure over ice.
When condensation forms
Water collects on any surface that is at or below the dew point of the air touching it. Window glass and outer wall corners in winter, and chilled-water pipes and ducts in summer, are the usual places. A surface warmer than the dew point stays dry.
Example: window condensation in winter
Room air at 20 °C and 60 % RH has a dew point of about 12.0 °C. If the cold weather keeps the inner glass at 10 °C, that is below the dew point, so condensation forms.
To keep that window dry, lower the room humidity to about 52.5 % or less, or keep the glass warmer than 12.0 °C.
How to reduce condensation
- Ventilate: remove moisture from cooking, showers and drying laundry to lower the room humidity.
- Manage humidity: do not over-humidify in winter, and dehumidify if needed.
- Keep surfaces warm: double or low-e glazing, added insulation, and letting air reach behind curtains. Insulate chilled-water pipes so their outer surface stays above the dew point.
Dew point table (temperature × relative humidity)
Values in °C at sea-level pressure 101.325 kPa. Values below 0 °C are frost points (over ice). A surface at or below the value collects condensation.
| Temperature | RH 30 % | RH 40 % | RH 50 % | RH 60 % | RH 70 % | RH 80 % | RH 90 % |
|---|---|---|---|---|---|---|---|
| 10 °C | −6.0 | −2.6 | 0.1 | 2.6 | 4.8 | 6.7 | 8.4 |
| 15 °C | −2.1 | 1.5 | 4.7 | 7.3 | 9.6 | 11.6 | 13.4 |
| 18 °C | 0.2 | 4.2 | 7.4 | 10.1 | 12.5 | 14.5 | 16.3 |
| 20 °C | 1.9 | 6.0 | 9.3 | 12.0 | 14.4 | 16.4 | 18.3 |
| 22 °C | 3.6 | 7.8 | 11.1 | 13.9 | 16.3 | 18.4 | 20.3 |
| 24 °C | 5.4 | 9.6 | 12.9 | 15.8 | 18.2 | 20.3 | 22.3 |
| 26 °C | 7.1 | 11.4 | 14.8 | 17.6 | 20.1 | 22.3 | 24.2 |
| 28 °C | 8.8 | 13.2 | 16.6 | 19.5 | 22.0 | 24.2 | 26.2 |
| 30 °C | 10.5 | 14.9 | 18.4 | 21.4 | 23.9 | 26.2 | 28.2 |
| 35 °C | 14.8 | 19.4 | 23.0 | 26.1 | 28.7 | 31.0 | 33.1 |
Frequently asked questions
How is the dew point calculated?
Find the saturation vapor pressure at the air temperature, multiply by the relative humidity to get the actual vapor pressure, then find the temperature whose saturation pressure equals it. This page solves the Hyland-Wexler equations from ASHRAE Fundamentals 2017 chapter 1 backwards.
What is the dew point at 20 °C and 60 % RH indoors?
About 12.0 °C. Window glass or a wall surface at or below about 12 °C collects condensation. At 50 % RH it drops to about 9.3 °C, and at 40 % to about 6.0 °C.
How do I tell whether a chilled-water pipe needs insulation?
Compare the pipe's outer surface temperature with the dew point of the surrounding air. Air at 26 °C and 50 % has a dew point of about 14.8 °C, so a bare pipe carrying 7 °C water will sweat. Choose an insulation thickness that keeps its outer face above the dew point.
How are dew point and condensation related?
When air touches a surface colder than its dew point, water vapor condenses there. A surface at or below the dew point collects condensation; above it, none forms. At the same temperature, higher humidity raises the dew point, so condensation forms more easily (at 20 °C: about 6.0 °C at 40 % RH, about 12.0 °C at 60 %).
How do I size pipe insulation thickness to prevent condensation?
Find the dew point from room temperature and humidity, then the thinnest insulation whose outer surface is above it by a margin (usually 1 K). The surface gets warmer as conductivity falls, thickness rises and jacket emissivity rises. In the calculator above, pick the material and thickness to see the surface temperature, the verdict and the minimum thickness (rounded up to a standard size); the table above covers SGP 15A to 100A directly.
Why is an aluminium jacket worse for condensation?
The outer surface gains heat by convection from the air and by radiation from the surroundings. Aluminium has an emissivity of about 0.05, so it gains almost no radiant heat, the outer coefficient drops and the surface runs colder. For a 50A pipe with 7 °C water, 25 mm glass wool and 30 °C, 80 % room air, a non-metal finish gives a surface near 27.4 °C, above the 26.2 °C dew point, but a new aluminium jacket drops it to about 24.8 °C and condensation forms.
What safety margin should I use for the condensation check?
A surface at or below the dew point condenses. To allow for workmanship, humidity swings and thermal bridges at joints and hangers, designers commonly keep the surface 1 to 2 K above the dew point (a practice, not a fixed standard). The calculator defaults to 1 K and you can change it in the Safety margin field; anything below it is shown as At risk.
Equations and sources
The same equations as the calculator engine. T = t + 273.15 K, p = pressure in Pa.
| Item | Equation | Notes · basis |
|---|---|---|
| Saturation pressure (water) | ln pws = C8/T + C9 + C10·T + C11·T² + C12·T³ + C13·ln T | ASHRAE Eq. 6 (Hyland-Wexler), 0.01 to 200 °C |
| Saturation pressure (ice) | ln pws = C1/T + C2 + C3·T + C4·T² + C5·T³ + C6·T⁴ + C7·ln T | ASHRAE Eq. 5 (Hyland-Wexler), −100 to 0.01 °C |
| Vapor pressure and humidity ratio | pw = RH/100 · pws(t), W = 0.621945 · pw / (p − pw) | ASHRAE Eq. 20 |
| Dew point (frost point) | pws(td) = pw | Inverse of Eq. 5 and 6 by Newton iteration; ice form (frost point) when td ≤ 0.01 °C |
| Condensation and margin | condensation ⇔ ts ≤ td, margin = ts − td | Condensation when the air at the surface reaches saturation (same definition as the calculator's condensation check) |
| Surface RH and highest RH | RHs = 100 · pw / pws(ts), RHmax = 100 · pws(ts) / pws(t) | RHmax: the RH at the same room temperature whose dew point equals the surface (same definition as the calculator's condensation check) |
Sources
- ASHRAE Handbook Fundamentals 2017 (SI), chapter 1 Psychrometrics: Eq. 5 and 6 saturation pressure, Eq. 20 humidity ratio
- Hyland, R. W. and Wexler, A. (1983), Formulations for the thermodynamic properties of the saturated phases of H2O from 173.15 K to 473.15 K, ASHRAE Transactions 89(2A)
Insulation surface condensation and the pipe insulation thickness that prevents it
Wrapping a chilled pipe does not help if the outer surface stays at or below the dew point of the surrounding air: water then forms on the insulation (surface condensation). The surface temperature is set where two things balance: how well the insulation resists heat (conductivity k, thickness t) and how much heat the air delivers to the surface (the combined convection and radiation coefficient hse).
To size the insulation, solve that balance for the surface temperature Ts and compare it with the dew point Td. If Ts is above Td there is no condensation, and Ts − Td is the margin. The calculator above handles pipes (cylinders) and flat surfaces (ducts, equipment), finds the minimum thickness by bisection and rounds it up to a standard size.
The jacket matters too. A low-emissivity jacket such as aluminium exchanges almost no radiant heat with its surroundings, so the surface stays colder and is worse for condensation at the same thickness. Elastomeric insulation is often used without a jacket and has a surface emissivity of about 0.9.
Minimum insulation thickness to prevent condensation on chilled-water pipe (SGP 15A to 100A)
Minimum thickness (mm, rounded up) that prevents condensation at room air 30 °C and 80 % RH, 7 °C chilled water, still indoor air and a 1 K margin. Values come from the same engine as the calculator. In practice pick the next standard size (10, 13, 15, 20, 25, 30, 40, 50, 65, 75, 100 mm).
| Size | Outside dia. mm | Glass wool | Elastomeric | Rigid PU | |||
|---|---|---|---|---|---|---|---|
| ε 0.9 | ε 0.05 | ε 0.9 | ε 0.05 | ε 0.9 | ε 0.05 | ||
| 15A | 21.7 | 18 | 40 | 18 | 40 | 14 | 31 |
| 20A | 27.2 | 19 | 43 | 19 | 43 | 15 | 33 |
| 25A | 34 | 20 | 46 | 20 | 46 | 16 | 35 |
| 32A | 42.7 | 21 | 50 | 21 | 49 | 17 | 38 |
| 40A | 48.6 | 22 | 52 | 22 | 51 | 17 | 39 |
| 50A | 60.5 | 23 | 55 | 23 | 55 | 18 | 42 |
| 65A | 76.3 | 24 | 59 | 24 | 59 | 19 | 45 |
| 80A | 89.1 | 25 | 62 | 25 | 62 | 19 | 47 |
| 90A | 101.6 | 26 | 65 | 25 | 64 | 19 | 49 |
| 100A | 114.3 | 26 | 67 | 26 | 67 | 20 | 51 |
ε 0.9 is a non-metal finish (PVC, paint, canvas, rubber); ε 0.05 is new aluminium foil. An aluminium jacket needs much more thickness on the same insulation. > 500 means even 500 mm is not enough.
Equations
Steady-state heat transfer in the form of ISO 12241, per metre of pipe or per m² of flat surface.
| Item | Equation | Notes · basis |
|---|---|---|
| Heat balance (surface temperature Ts) | (Ta − Ts) / Rse = (Ts − Tf) / Rins | Ts is solved by bisection; for chilled water Tf < Ts < Ta |
| Resistances (cylinder / flat) | Rins = ln(D2/D1) / (2πk), Rse = 1 / (hse · π · D2), D2 = D1 + 2t. Flat: Rins = t/k, Rse = 1/hse | Pipe wall and inner film are neglected (conservative) |
| Outer film coefficient | hse = hcv + hr | Convection plus radiation |
| Radiative coefficient | hr = ε · σ · (Ts⁴ − Ta⁴) / (Ts − Ta) | σ = 5.670×10⁻⁸ W/m²K⁴, temperatures in K. ε is the jacket surface emissivity |
| Natural convection (still indoor air) | Horizontal pipe: 1.25 (ΔT/D2)^0.25 (D2³ΔT ≤ 10), otherwise 1.21 ΔT^(1/3). Vertical plane (H = 1 m): 1.42 (ΔT/H)^0.25, otherwise 1.31 ΔT^(1/3) | With wind, combined with forced convection (Churchill-Bernstein). The constants were not checked against the standard text; review before design use |
| Conductivity vs temperature | k = k10 + a · (Tm − 10), Tm = (Tf + Ts) / 2 | k10: value at 10 °C mean, a: slope (table below) |
| Verdict | condensation ⇔ Ts ≤ Td, at risk ⇔ Ts − Td < margin, safe ⇔ Ts − Td ≥ margin | Td from the dew point equations above (ASHRAE 2017). Default margin 1 K |
Typical insulation conductivity (design reference values)
Conductivity k10 at 10 °C mean temperature and temperature slope a. Values vary by maker and grade; override them with the product datasheet.
| Material | k10 W/m·K | a W/m·K² | Vapour barrier for cold service | Basis |
|---|---|---|---|---|
| Glass wool (board, pipe section) | 0.034 | 0.00015 | Separate barrier needed | KS L 9102 glass wool 24K, 0.043 or less at 70 °C mean |
| Rock wool (board, pipe section) | 0.034 | 0.00018 | Separate barrier needed | Rock wool about 0.045 at 70 °C mean (varies) |
| Elastomeric foam (NBR, EPDM) | 0.034 | 0.0001 | Closed cell (glue the joints) | EN 14304: 0.033 or less at 0 °C, about 0.036 at 40 °C |
| Polyethylene foam | 0.036 | 0.00012 | Closed cell (glue the joints) | Manufacturer data 0.035 to 0.040 |
| Rigid polyurethane (PU, PIR) | 0.025 | 0.0001 | Closed cell (glue the joints) | Aged design value for rigid PU and PIR |
| Phenolic foam | 0.024 | 0.00008 | Closed cell (glue the joints) | KS M 3808 0.022 or less; aged design value |
| Extruded polystyrene (XPS) | 0.034 | 0.0001 | Closed cell (glue the joints) | EN 13164 declared 0.030 to 0.036 |
Jacket (finish) surface emissivity
| Jacket | Emissivity ε |
|---|---|
| Aluminium foil or sheet (new) | 0.05 |
| Aluminium (oxidised) | 0.13 |
| Galvanised steel | 0.26 |
| Stainless steel | 0.15 |
| PVC, paint, canvas, elastomer surface | 0.9 |
Last updated 2026-11-23.