Dew point calculator and condensation check

Get the dew point from room temperature and relative humidity. Add the surface temperature of a window, wall or chilled-water pipe to see whether condensation forms and how far to lower the humidity to stop it. Below, choose the insulation material and thickness to check surface condensation on insulated pipe and get the minimum thickness that prevents it.

What the dew point is

Air can hold only so much water vapor; when it cools, the extra comes out as droplets. The temperature where that starts is the dew point. At the same temperature, more humid air has a higher dew point.

Below 0 °C the vapor turns to ice (frost) instead of water, so it is called the frost point and is computed with the saturation pressure over ice.

When condensation forms

Water collects on any surface that is at or below the dew point of the air touching it. Window glass and outer wall corners in winter, and chilled-water pipes and ducts in summer, are the usual places. A surface warmer than the dew point stays dry.

Example: window condensation in winter

Room air at 20 °C and 60 % RH has a dew point of about 12.0 °C. If the cold weather keeps the inner glass at 10 °C, that is below the dew point, so condensation forms.

To keep that window dry, lower the room humidity to about 52.5 % or less, or keep the glass warmer than 12.0 °C.

How to reduce condensation

Dew point table (temperature × relative humidity)

Values in °C at sea-level pressure 101.325 kPa. Values below 0 °C are frost points (over ice). A surface at or below the value collects condensation.

TemperatureRH 30 %RH 40 %RH 50 %RH 60 %RH 70 %RH 80 %RH 90 %
10 °C−6.0−2.60.12.64.86.78.4
15 °C−2.11.54.77.39.611.613.4
18 °C0.24.27.410.112.514.516.3
20 °C1.96.09.312.014.416.418.3
22 °C3.67.811.113.916.318.420.3
24 °C5.49.612.915.818.220.322.3
26 °C7.111.414.817.620.122.324.2
28 °C8.813.216.619.522.024.226.2
30 °C10.514.918.421.423.926.228.2
35 °C14.819.423.026.128.731.033.1

Frequently asked questions

How is the dew point calculated?

Find the saturation vapor pressure at the air temperature, multiply by the relative humidity to get the actual vapor pressure, then find the temperature whose saturation pressure equals it. This page solves the Hyland-Wexler equations from ASHRAE Fundamentals 2017 chapter 1 backwards.

What is the dew point at 20 °C and 60 % RH indoors?

About 12.0 °C. Window glass or a wall surface at or below about 12 °C collects condensation. At 50 % RH it drops to about 9.3 °C, and at 40 % to about 6.0 °C.

How do I tell whether a chilled-water pipe needs insulation?

Compare the pipe's outer surface temperature with the dew point of the surrounding air. Air at 26 °C and 50 % has a dew point of about 14.8 °C, so a bare pipe carrying 7 °C water will sweat. Choose an insulation thickness that keeps its outer face above the dew point.

How are dew point and condensation related?

When air touches a surface colder than its dew point, water vapor condenses there. A surface at or below the dew point collects condensation; above it, none forms. At the same temperature, higher humidity raises the dew point, so condensation forms more easily (at 20 °C: about 6.0 °C at 40 % RH, about 12.0 °C at 60 %).

How do I size pipe insulation thickness to prevent condensation?

Find the dew point from room temperature and humidity, then the thinnest insulation whose outer surface is above it by a margin (usually 1 K). The surface gets warmer as conductivity falls, thickness rises and jacket emissivity rises. In the calculator above, pick the material and thickness to see the surface temperature, the verdict and the minimum thickness (rounded up to a standard size); the table above covers SGP 15A to 100A directly.

Why is an aluminium jacket worse for condensation?

The outer surface gains heat by convection from the air and by radiation from the surroundings. Aluminium has an emissivity of about 0.05, so it gains almost no radiant heat, the outer coefficient drops and the surface runs colder. For a 50A pipe with 7 °C water, 25 mm glass wool and 30 °C, 80 % room air, a non-metal finish gives a surface near 27.4 °C, above the 26.2 °C dew point, but a new aluminium jacket drops it to about 24.8 °C and condensation forms.

What safety margin should I use for the condensation check?

A surface at or below the dew point condenses. To allow for workmanship, humidity swings and thermal bridges at joints and hangers, designers commonly keep the surface 1 to 2 K above the dew point (a practice, not a fixed standard). The calculator defaults to 1 K and you can change it in the Safety margin field; anything below it is shown as At risk.

Equations and sources

The same equations as the calculator engine. T = t + 273.15 K, p = pressure in Pa.

ItemEquationNotes · basis
Saturation pressure (water)ln pws = C8/T + C9 + C10·T + C11·T² + C12·T³ + C13·ln TASHRAE Eq. 6 (Hyland-Wexler), 0.01 to 200 °C
Saturation pressure (ice)ln pws = C1/T + C2 + C3·T + C4·T² + C5·T³ + C6·T⁴ + C7·ln TASHRAE Eq. 5 (Hyland-Wexler), −100 to 0.01 °C
Vapor pressure and humidity ratiopw = RH/100 · pws(t), W = 0.621945 · pw / (p − pw)ASHRAE Eq. 20
Dew point (frost point)pws(td) = pwInverse of Eq. 5 and 6 by Newton iteration; ice form (frost point) when td ≤ 0.01 °C
Condensation and margincondensation ⇔ ts ≤ td, margin = ts − tdCondensation when the air at the surface reaches saturation (same definition as the calculator's condensation check)
Surface RH and highest RHRHs = 100 · pw / pws(ts), RHmax = 100 · pws(ts) / pws(t)RHmax: the RH at the same room temperature whose dew point equals the surface (same definition as the calculator's condensation check)

Sources

Insulation surface condensation and the pipe insulation thickness that prevents it

Wrapping a chilled pipe does not help if the outer surface stays at or below the dew point of the surrounding air: water then forms on the insulation (surface condensation). The surface temperature is set where two things balance: how well the insulation resists heat (conductivity k, thickness t) and how much heat the air delivers to the surface (the combined convection and radiation coefficient hse).

To size the insulation, solve that balance for the surface temperature Ts and compare it with the dew point Td. If Ts is above Td there is no condensation, and Ts − Td is the margin. The calculator above handles pipes (cylinders) and flat surfaces (ducts, equipment), finds the minimum thickness by bisection and rounds it up to a standard size.

The jacket matters too. A low-emissivity jacket such as aluminium exchanges almost no radiant heat with its surroundings, so the surface stays colder and is worse for condensation at the same thickness. Elastomeric insulation is often used without a jacket and has a surface emissivity of about 0.9.

Minimum insulation thickness to prevent condensation on chilled-water pipe (SGP 15A to 100A)

Minimum thickness (mm, rounded up) that prevents condensation at room air 30 °C and 80 % RH, 7 °C chilled water, still indoor air and a 1 K margin. Values come from the same engine as the calculator. In practice pick the next standard size (10, 13, 15, 20, 25, 30, 40, 50, 65, 75, 100 mm).

SizeOutside dia. mmGlass woolElastomericRigid PU
ε 0.9ε 0.05ε 0.9ε 0.05ε 0.9ε 0.05
15A21.7184018401431
20A27.2194319431533
25A34204620461635
32A42.7215021491738
40A48.6225222511739
50A60.5235523551842
65A76.3245924591945
80A89.1256225621947
90A101.6266525641949
100A114.3266726672051

ε 0.9 is a non-metal finish (PVC, paint, canvas, rubber); ε 0.05 is new aluminium foil. An aluminium jacket needs much more thickness on the same insulation. > 500 means even 500 mm is not enough.

Equations

Steady-state heat transfer in the form of ISO 12241, per metre of pipe or per m² of flat surface.

ItemEquationNotes · basis
Heat balance (surface temperature Ts)(Ta − Ts) / Rse = (Ts − Tf) / RinsTs is solved by bisection; for chilled water Tf < Ts < Ta
Resistances (cylinder / flat)Rins = ln(D2/D1) / (2πk), Rse = 1 / (hse · π · D2), D2 = D1 + 2t. Flat: Rins = t/k, Rse = 1/hsePipe wall and inner film are neglected (conservative)
Outer film coefficienthse = hcv + hrConvection plus radiation
Radiative coefficienthr = ε · σ · (Ts⁴ − Ta⁴) / (Ts − Ta)σ = 5.670×10⁻⁸ W/m²K⁴, temperatures in K. ε is the jacket surface emissivity
Natural convection (still indoor air)Horizontal pipe: 1.25 (ΔT/D2)^0.25 (D2³ΔT ≤ 10), otherwise 1.21 ΔT^(1/3). Vertical plane (H = 1 m): 1.42 (ΔT/H)^0.25, otherwise 1.31 ΔT^(1/3)With wind, combined with forced convection (Churchill-Bernstein). The constants were not checked against the standard text; review before design use
Conductivity vs temperaturek = k10 + a · (Tm − 10), Tm = (Tf + Ts) / 2k10: value at 10 °C mean, a: slope (table below)
Verdictcondensation ⇔ Ts ≤ Td, at risk ⇔ Ts − Td < margin, safe ⇔ Ts − Td ≥ marginTd from the dew point equations above (ASHRAE 2017). Default margin 1 K

Typical insulation conductivity (design reference values)

Conductivity k10 at 10 °C mean temperature and temperature slope a. Values vary by maker and grade; override them with the product datasheet.

Materialk10 W/m·Ka W/m·K²Vapour barrier for cold serviceBasis
Glass wool (board, pipe section)0.0340.00015Separate barrier neededKS L 9102 glass wool 24K, 0.043 or less at 70 °C mean
Rock wool (board, pipe section)0.0340.00018Separate barrier neededRock wool about 0.045 at 70 °C mean (varies)
Elastomeric foam (NBR, EPDM)0.0340.0001Closed cell (glue the joints)EN 14304: 0.033 or less at 0 °C, about 0.036 at 40 °C
Polyethylene foam0.0360.00012Closed cell (glue the joints)Manufacturer data 0.035 to 0.040
Rigid polyurethane (PU, PIR)0.0250.0001Closed cell (glue the joints)Aged design value for rigid PU and PIR
Phenolic foam0.0240.00008Closed cell (glue the joints)KS M 3808 0.022 or less; aged design value
Extruded polystyrene (XPS)0.0340.0001Closed cell (glue the joints)EN 13164 declared 0.030 to 0.036

Jacket (finish) surface emissivity

JacketEmissivity ε
Aluminium foil or sheet (new)0.05
Aluminium (oxidised)0.13
Galvanised steel0.26
Stainless steel0.15
PVC, paint, canvas, elastomer surface0.9

Last updated 2026-11-23.