Psychrometric chart online and calculator

psychart.kr is a free online psychrometric chart for HVAC engineers and engineering students. Click the chart or enter any two values to get dry-bulb, relative humidity, humidity ratio, enthalpy, wet-bulb, dew point, specific volume, density and vapor pressure. Calculations follow ASHRAE Handbook Fundamentals 2017.

psychart.kr psychrometric chart calculator: cooling process from mixed air MA (outdoor + room air) through the cooling coil to supply air SA, with total, sensible and latent kW
Cooling example: outdoor air 32 °C, 60 % mixed with room air 26 °C, 50 % (MA), cooled by the coil to SA. Total 39.92 kW, condensate 23.0 kg/h
Free high-resolution psychrometric chart PDF & PNG download

How to read a psychrometric chart

  1. The horizontal axis is dry-bulb temperature (°C) and the right vertical axis is humidity ratio (g/kg dry air). A point is fixed by these two, and every other property is read from the lines through it.
  2. Curves rising from bottom left to top right are relative humidity lines, and the heavy top curve is 100 % saturation. The dew point is where a horizontal line from the point meets the saturation curve on the left.
  3. Diagonals falling from top left to bottom right are enthalpy lines (kJ/kg dry air), and the nearly parallel dashed lines are wet-bulb. The steep dotted lines are specific volume (m³/kg dry air).
  4. Processes: sensible heating and cooling move horizontally, humidifying and dehumidifying move vertically, and cooling with dehumidification at a coil moves down and to the left. A mixed state lies on the straight line between two points, split by the airflow ratio.
  5. Draw the sensible heat ratio (SHF) line through the room state with the slope from the protractor at top left. The supply air state must lie on this line to meet both the sensible and latent room loads.
  6. Older textbooks use kcal/kg and kg/kg′: 1 kcal/kg = 4.1868 kJ/kg and 1 kg/kg′ = 1,000 g/kg of dry air.

More on the six line families, processes, SHF and plotting steps

Try 18 psychrometric chart practice problems (graded, with plotting steps)

Key properties

Dry-bulb temperature (DB, °C)
Air temperature from an ordinary thermometer; the horizontal axis of the chart.
Wet-bulb temperature (WB, °C)
Temperature of a thermometer wrapped in a wet wick. Lower than dry-bulb by evaporative cooling, and equal to it in saturated air.
Dew point (DP, °C)
Temperature at which air starts to condense when cooled at constant moisture. Surfaces colder than this collect condensation.
Relative humidity (RH, %)
Water vapor present as a share of the most the air can hold at that temperature (by vapor pressure).
Humidity ratio (W, g/kg dry air)
Mass of water vapor per kg of dry air. It stays the same when temperature changes at constant moisture.
Enthalpy (h, kJ/kg dry air)
Heat content of 1 kg of dry air and its water vapor. Coil load = mass flow × enthalpy difference.
Specific volume (v, m³/kg dry air)
Volume taken by 1 kg of dry air with its vapor. Converts m³/h airflow to mass flow.
Sensible heat ratio (SHF)
Sensible share of the total heat. The room SHF sets the slope of the line the supply air state must lie on.

How to use

  1. Click the chart to add a state point (A, B, C …). Hovering shows the properties at the cursor right next to it.
  2. In the panel, pick the two defining values (for example dry-bulb and RH) and type numbers. The result updates as you type and the point moves on the chart.
  3. Drag points to move them, delete them from the point list, and undo with Ctrl+Z.
  4. Connect two points (point menu "Connect from here" or Shift+drag) to make a process. Enter an airflow to get total, sensible and latent kW and condensate. "Mix" creates the mixed state of two airstreams.
  5. Use "Copy table" to paste results into Excel, or "Export" for CSV, images or a printed report (PDF).

Equations (ASHRAE 2017, SI)

Frequently asked questions

What is a psychrometric chart?

A single graph of the state of moist air. The horizontal axis is dry-bulb temperature and the vertical axis is humidity ratio (grams of water vapor per kilogram of dry air). Lines of relative humidity, enthalpy, wet-bulb temperature and specific volume are drawn on top, so knowing any two values lets you read all the others.

It is used for HVAC design, cooling coil and humidifier selection, building environment control and condensation checks.

How do I read a psychrometric chart?

(1) Dry-bulb is read on the bottom axis along vertical lines, (2) humidity ratio on the right axis along horizontal lines, (3) relative humidity follows the dark red curves rising to the right (the bold black outer curve is 100 %, saturation), (4) enthalpy runs down to the right in green from the scale outside the saturation curve, (5) wet-bulb is the teal dashed line almost parallel to enthalpy, and (6) specific volume is the steep grey-violet dotted line.

The dew point is where a horizontal line from the point meets the saturation curve. In this calculator, hovering shows all values in a card next to the cursor.

Which equations does this calculator use? How accurate is it?

It uses the equations of ASHRAE Handbook Fundamentals 2017, chapter 1: Hyland-Wexler saturation pressure, with wet-bulb and dew point solved iteratively rather than approximated.

The engine is our own and is checked automatically against PsychroLib, an open library that implements the same ASHRAE equations: temperatures agree within 0.001 °C and humidity ratio, enthalpy and specific volume within a relative error of 1e-9. For very dry air with a wet-bulb near 0 °C, the water/ice switch in the ASHRAE equations can make the wet-bulb slightly ambiguous.

What are the properties at 25 °C dry-bulb and 50 % RH?

At 101.325 kPa: humidity ratio 9.88 g/kg, enthalpy 50.3 kJ/kg, wet-bulb 17.9 °C, dew point 13.9 °C, specific volume 0.858 m³/kg, density 1.177 kg/m³ and vapor pressure 1,585 Pa.

Which two values define a state point?

Any two independent values among dry-bulb, relative humidity, wet-bulb, dew point, humidity ratio, enthalpy and specific volume (24 combinations). Pairs that carry the same information, such as humidity ratio and dew point, and states above saturation (over 100 % RH) are rejected with the reason.

Example: 30 °C dry-bulb and 22 °C wet-bulb give 50.0 % RH, 18.4 °C dew point and 13.30 g/kg humidity ratio.

How are cooling coil load (kW) and condensate calculated?

Total = dry-air mass flow × (outlet enthalpy − inlet enthalpy), sensible = mass flow × (1.006 + 1.86 × inlet humidity ratio) × temperature difference, latent = total − sensible, condensate = mass flow × humidity ratio difference.

Example: cooling 33 °C/60 % air to 26 °C/50 % at 3,600 kg/h of dry air gives 29.25 kW total, 7.29 kW sensible, 21.96 kW latent, SHF 0.25 and 31.0 kg/h of condensate. At 10,000 CMH (inlet conditions) it is 90.9 kW and 96.4 kg/h.

In this calculator, connect two points and enter the airflow.

See all questions