Saiz paip stim
Masukkan tekanan tolok dan aliran stim untuk mendapat saiz yang disyorkan mengikut halaju atau kehilangan tekanan. Semua andaian dan sumber disenaraikan di bawah.
Pengesahan: perbandingan dengan nilai diterbitkan
Input yang sama dijalankan melalui Spirax Sarco, TLV dan contoh lapangan Korea, dan dibandingkan dengan kalkulator ini. Kehilangan tekanan boleh berbeza beberapa peratus kerana kekasaran yang diandaikan.
| Item | Nilai diterbitkan | Nilai kalkulator | Sumber |
|---|---|---|---|
| T4 | |||
| V (150A, 6,989 kg/h) | 25.000 m/s | 24.993 m/s | Spirax Sarco, Pipes and Pipe Sizing 표 10.2.4 (ASME Sch40 기준) |
| T5 | |||
| 필요 안지름 | 130.3 mm | 130.3 mm | Spirax Sarco, Pipes and Pipe Sizing 예제 10.2.4 |
| asme40 150A 유속 | 17.880 m/s | 17.880 m/s | Spirax Sarco, Pipes and Pipe Sizing 예제 10.2.4 |
| T6a | |||
| 유속 | 17.880 m/s | 17.880 m/s | TLV 계산기 (유속법), 2026-10-26 직접 실행 |
| 100 m 손실 (우리는 거칠기 0.046 mm 로 TLV 보다 약 2 % 낮음) | 0.0699 bar | 0.0685 bar | TLV 계산기 (유속법), 2026-10-26 직접 실행 |
| T6b | |||
| 유속 (150A) | 18.610 m/s | 18.610 m/s | TLV 계산기 (유속법), 2026-10-26 직접 실행 |
| 100 m 손실 | 0.0774 bar | 0.0758 bar | TLV 계산기 (유속법), 2026-10-26 직접 실행 |
| T6c | |||
| 유속 (65A) | 24.531 m/s | 24.531 m/s | TLV 계산기 (유속법), 2026-10-26 직접 실행 |
| 100 m 손실 | 0.2686 bar | 0.2625 bar | TLV 계산기 (유속법), 2026-10-26 직접 실행 |
| T6d | |||
| 유속 (100A) | 21.286 m/s | 21.286 m/s | TLV 계산기 (유속법), 2026-10-26 직접 실행 (90A 제외 확인) |
| 100 m 손실 | 0.1248 bar | 0.1221 bar | TLV 계산기 (유속법), 2026-10-26 직접 실행 (90A 제외 확인) |
| T6e | |||
| 유속 (40A, 1-1/2") | 23.308 m/s | 23.309 m/s | TLV 계산기 (유속법, IP 입력), 2026-10-26 직접 실행 |
| T6f | |||
| 유속 (80A, 3") | 43.006 m/s | 43.006 m/s | TLV 계산기 (압력손실법, IP 입력), 2026-10-26 직접 실행 |
| T7 | |||
| 필요 안지름 | 39.710 mm | 39.710 mm | Spirax Sarco 예제 10.2.2 (압력손실 기준), TLV [3] |
| stpg40 40A 유속 | 13.499 m/s | 13.499 m/s | Spirax Sarco 예제 10.2.2 (압력손실 기준), TLV [3] |
| stpg40 40A 165 m 손실 | 0.3312 bar | 0.3312 bar | Spirax Sarco 예제 10.2.2 (압력손실 기준), TLV [3] |
| T8 | |||
| 유속 (65A, 2-1/2", ASHRAE 「약 13,000 fpm」) | 13,000.0 ft/min | 13,072.0 ft/min | ASHRAE 1997 Fundamentals 증기 배관 예제 (Armstrong Steam Conservation Guidelines CG-25 재수록) |
| T9 | |||
| 필요 안지름 | 81.310 mm | 81.308 mm | 국내 실무 블로그 예제 (참고용, [10]) |
| stpg40 100A 유속 | 15.793 m/s | 15.793 m/s | 국내 실무 블로그 예제 (참고용, [10]) |
Asas pengiraan
Berdasarkan stim tepu kering (kualiti x = 1). Sifat tepu daripada interpolasi jadual IAPWS-IF97; halaju dan kehilangan tekanan menggunakan persamaan Darcy-Weisbach + Colebrook yang sama seperti kalkulator saluran/paip.
| Item | Persamaan | Nota |
|---|---|---|
| Tekanan mutlak | p_abs = p_g + 101.325 kPa | Menambah tekanan atmosfera piawai 101.325 kPa |
| Sifat tepu | T_sat, v_f, v_g, h_f, h_g = f(p_abs) | Interpolasi Lagrange 4 titik dalam ln(p) |
| Aliran jisim | ṁ = q, 또는 ṁ = 3600 · Q(kW) / h_fg | Untuk kuasa haba (kW, MBH), bahagi dengan haba laten h_fg |
| Aliran isipadu | Q = ṁ · v_g | Aliran jisim × isipadu khusus v_g |
| Diameter dalaman dari halaju | D = √(4Q / (πV)) | Terus dari halaju reka bentuk |
| Diameter dalaman dari kehilangan tekanan | R(D) = R_target | R(D) = sasaran diselesaikan dengan biseksi dalam log D (sama seperti kalkulator paip) |
| Nombor Reynolds dan faktor geseran | 1/√f = −2 log₁₀( ε/(3.7D) + 2.51/(Re√f) ) | Persamaan Colebrook (penyelesai sama seperti saluran/paip) |
Jadual saiz paip
Pilih spesifikasi paip untuk lihat diameter luar, ketebalan dinding dan diameter dalaman setiap saiz.
STPG Sch40 (KS D 3562 / JIS G3454)
Paip keluli karbon tekanan KS D 3562 / JIS G 3454 Sch40. Lalai kalkulator ini.
| Saiz | Dia. luar mm | Dinding mm | Lubang mm |
|---|---|---|---|
| 15A | 21.7 | 2.8 | 16.1 |
| 20A | 27.2 | 2.9 | 21.4 |
| 25A | 34.0 | 3.4 | 27.2 |
| 32A | 42.7 | 3.6 | 35.5 |
| 40A | 48.6 | 3.7 | 41.2 |
| 50A | 60.5 | 3.9 | 52.7 |
| 65A | 76.3 | 5.2 | 65.9 |
| 80A | 89.1 | 5.5 | 78.1 |
| 100A | 114.3 | 6.0 | 102.3 |
| 125A | 139.8 | 6.6 | 126.6 |
| 150A | 165.2 | 7.1 | 151.0 |
| 200A | 216.3 | 8.2 | 199.9 |
| 250A | 267.4 | 9.3 | 248.8 |
| 300A | 318.5 | 10.3 | 297.9 |
SGP (KS D 3507 / JIS G3452)
Paip keluli karbon KS D 3507 / JIS G 3452 (SPP/SGP). Hanya di bawah 1 MPa (KDS 31 25 25:2021).
| Saiz | Dia. luar mm | Dinding mm | Lubang mm |
|---|---|---|---|
| 15A | 21.7 | 2.8 | 16.1 |
| 20A | 27.2 | 2.8 | 21.6 |
| 25A | 34.0 | 3.2 | 27.6 |
| 32A | 42.7 | 3.5 | 35.7 |
| 40A | 48.6 | 3.5 | 41.6 |
| 50A | 60.5 | 3.8 | 52.9 |
| 65A | 76.3 | 4.2 | 67.9 |
| 80A | 89.1 | 4.2 | 80.7 |
| 100A | 114.3 | 4.5 | 105.3 |
| 125A | 139.8 | 4.5 | 130.8 |
| 150A | 165.2 | 5.0 | 155.2 |
| 200A | 216.3 | 5.8 | 204.7 |
| 250A | 267.4 | 6.6 | 254.2 |
| 300A | 318.5 | 6.9 | 304.7 |
ASME B36.10M Sch40
ASME B36.10M Sch40 (saiz inci).
| Saiz | Dia. luar mm | Dinding mm | Lubang mm |
|---|---|---|---|
| 15A (1/2) | 21.34 | 2.77 | 15.8 |
| 20A (3/4) | 26.67 | 2.87 | 20.93 |
| 25A (1) | 33.4 | 3.38 | 26.65 |
| 32A (1-1/4) | 42.16 | 3.56 | 35.05 |
| 40A (1-1/2) | 48.26 | 3.68 | 40.89 |
| 50A (2) | 60.33 | 3.91 | 52.5 |
| 65A (2-1/2) | 73.03 | 5.16 | 62.71 |
| 80A (3) | 88.9 | 5.49 | 77.93 |
| 100A (4) | 114.3 | 6.02 | 102.26 |
| 125A (5) | 141.3 | 6.55 | 128.19 |
| 150A (6) | 168.28 | 7.11 | 154.05 |
| 200A (8) | 219.08 | 8.18 | 202.72 |
| 250A (10) | 273.05 | 9.27 | 254.51 |
| 300A (12) | 323.85 | 10.31 | 303.23 |
Kekasaran paip ε
Nilai bahan daripada carta faktor geseran Moody 1944, ditukar kepada mm. Kekasaran bertambah dengan usia dan kualiti air, jadi masukkan nilai lain dengan Tersuai.
| Bahan | ε (mm) | Nilai asal Moody |
|---|---|---|
| Keluli komersial | 0.046 | 0.00015 ft |
| Keluli bergalvani | 0.15 | 0.0005 ft |
| Tiub tarik (kuprum, loyang) | 0.0015 | 0.000005 ft |
Jadual stim tepu (IAPWS-IF97)
Jadual yang sama digunakan oleh kalkulator (iapws 1.5.5, sepadan CoolProp IF97 15 digit).
| Tekanan (mutlak) kPa | Suhu tepu °C | Isipadu khusus v_g m³/kg | Haba laten h_fg kJ/kg |
|---|---|---|---|
| 10.0 | 45.8 | 14.67 | 2,392.1 |
| 15.0 | 54.0 | 10.02 | 2,372.4 |
| 20.0 | 60.1 | 7.648 | 2,357.5 |
| 30.0 | 69.1 | 5.229 | 2,335.3 |
| 40.0 | 75.9 | 3.993 | 2,318.5 |
| 50.0 | 81.3 | 3.240 | 2,304.7 |
| 70.0 | 89.9 | 2.365 | 2,282.7 |
| 101 | 100.0 | 1.673 | 2,256.5 |
| 150 | 111.4 | 1.159 | 2,226.0 |
| 200 | 120.2 | 0.8857 | 2,201.6 |
| 250 | 127.4 | 0.7187 | 2,181.2 |
| 300 | 133.5 | 0.6058 | 2,163.4 |
| 400 | 143.6 | 0.4624 | 2,133.3 |
| 500 | 151.8 | 0.3748 | 2,107.9 |
| 600 | 158.8 | 0.3156 | 2,085.6 |
| 700 | 165.0 | 0.2728 | 2,065.6 |
| 800 | 170.4 | 0.2403 | 2,047.3 |
| 1,000 | 179.9 | 0.1943 | 2,014.4 |
| 1,200 | 188.0 | 0.1633 | 1,985.3 |
| 1,400 | 195.0 | 0.1408 | 1,958.8 |
| 1,600 | 201.4 | 0.1237 | 1,934.3 |
| 2,000 | 212.4 | 0.0996 | 1,889.8 |
| 2,500 | 224.0 | 0.0799 | 1,840.1 |
| 3,000 | 233.9 | 0.0667 | 1,794.9 |
| 3,500 | 242.6 | 0.0571 | 1,753.0 |
| 4,000 | 250.4 | 0.0498 | 1,713.5 |
| 4,500 | 257.4 | 0.0441 | 1,675.9 |
| 5,000 | 263.9 | 0.0394 | 1,639.7 |
Halaju dan kehilangan tekanan yang disyorkan
25 m/s untuk stim tepu dan 35 hingga 40 m/s untuk stim panas lampau ialah amalan biasa menurut Spirax Sarco dan TLV. Untuk kehilangan tekanan, 0.1 hingga 0.2 bar per 100 m (10 hingga 20 kPa) ialah julat biasa.
Had praktikal kira-kira 40 m/s; melebihi itu risiko bunyi dan hakisan meningkat. Untuk paip lebih 50 m, semak semula asas kehilangan tekanan walaupun sudah dipilih mengikut halaju.
Menurut KDS 31 25 25:2021, jumlah kehilangan tekanan tidak boleh melebihi satu pertiga tekanan tolok permulaan. Menurut Crane TP-410, apabila kehilangan melebihi kira-kira 10 % tekanan mutlak, andaian Darcy-Weisbach tak-mampat satu titik kurang tepat; bahagikan paip dan kira semula.
Sumber
- Spirax Sarco, Steam Engineering Tutorials, "Pipes and Pipe Sizing"
- TLV, Steam Line Sizing Calculator
- ASHRAE Handbook, Fundamentals (SI), chapter "Steam Systems"
- Crane Co., Technical Paper No. 410, "Flow of Fluids"
- Kementerian Tanah, Infrastruktur dan Pengangkutan (Korea), KDS 31 25 25:2021 "Piping Systems"
- IAPWS-IF97 (Persatuan Antarabangsa Sifat Air dan Stim), dikira dengan pakej iapws (1.5.5)
Soalan lazim
Bolehkah kalkulator ini untuk stim basah atau panas lampau?
Tidak. Hanya stim tepu kering (x = 1). Stim basah isipadu khusus lebih kecil, panas lampau lebih besar.
Mengapa sedikit berbeza daripada Spirax Sarco atau TLV?
Perbezaan kekasaran, pembundaran jadual dan interpolasi boleh menggeser kehilangan tekanan beberapa peratus. Halaju dan diameter diperlukan biasanya sepadan hingga perpuluhan. Lihat jadual pengesahan.
Bila SGP (paip hitam) tidak boleh digunakan?
Menurut KDS 31 25 25:2021, SGP (SPP) tidak boleh dari 1 MPa (10 kgf/cm², kira-kira 145 psi). Lebih tinggi pilih STPG atau paip tekanan.
Dikemas kini kali terakhir 2026-10-26.