High-altitude psychrometrics: what a sea-level chart gets wrong, and what it gets right
Most psychrometric charts are drawn for sea-level pressure, 101.325 kPa. Use the same chart on a site well above sea level and some readings stay valid while others drift. Taking 1,500 m as the example, this walks through reading field measurements, the room state, supply airflow and outdoor air coil load side by side with the sea-level answers, to show exactly what needs correcting.
Situation
Suppose you are designing the air handling for an office building on a plateau at 1,500 m above sea level. The outdoor design condition is given as 30 °C dry bulb with 20 °C wet bulb, the room is held at 24 °C and 50 %, and the room sensible load is 30 kW. Every chart and spreadsheet on your desk assumes sea level. The question is whether you can plot field readings from a sling psychrometer on that chart, and size airflow and coil load from its specific volume and enthalpy.
The short answer: relative humidity and dew point depend only on the partial pressure of water vapour, so for a given dry bulb and RH they do not change with altitude. Humidity ratio, enthalpy, specific volume, and anything you derive from a wet bulb reading do depend on barometric pressure. The rest of this article puts numbers on the difference and shows where it matters in a design.
Given
| Item | Value |
|---|---|
| Site elevation | 1,500 m (example). Standard atmosphere gives 84.56 kPa |
| Outdoor design O | 30 °C dry bulb, 20 °C wet bulb |
| Room R | 24 °C dry bulb, 50 % RH |
| Room sensible load | 30 kW, supply at 14 °C (10 K below the room, at the room humidity ratio, sensible only), supply-side fan |
| Outdoor air treatment | 3,000 CMH of outdoor air (at intake conditions) cooled and dehumidified to 14 °C / 90 % |
| Comparison | The same inputs solved at 101.325 kPa (what a sea-level chart would give) |
Plotting order on the chart
- Fix the site pressure first. Standard atmospheric pressure at 1,500 m is 84.56 kPa, 83.5 % of sea level. Set the chart or calculator to that pressure.
- Plot outdoor O from 30 °C dry bulb and 20 °C wet bulb. It lands at a higher humidity ratio than O0, the same two readings plotted on a sea-level chart.
- Plot room R from 24 °C and 50 % RH. The dew point matches sea level, but the humidity ratio sits above R0.
- Draw a line from O to the coil leaving state at 14 °C / 90 %. The enthalpy and humidity ratio differences along that line are the outdoor air coil load and condensate.
- The figure above is a sea-level (101.325 kPa) chart with the high-altitude points placed by their humidity ratio. Their position does not line up with the RH curves on that background, which is the point: high-altitude values have to be read from a chart or tool set to the site pressure.
Step by step
1) Barometric pressure. From the standard atmosphere, p = 101.325 × (1 − 2.25577×10−5 × 1,500)5.2559 = 84.56 kPa.
2) Outdoor air from dry bulb and wet bulb. Pressure appears in the wet bulb equation, so the same 30 °C / 20 °C reading means different air.
| Outdoor 30 °C / 20 °C wb | Sea-level chart O0 | 1,500 m O |
|---|---|---|
| Humidity ratio (g/kg) | 10.52 | 13.49 |
| Relative humidity (%) | 39.7 | 42.3 |
| Dew point (°C) | 14.8 | 15.8 |
| Enthalpy (kJ/kg) | 57.07 | 64.67 |
| Specific volume (m³/kg) | 0.8733 | 1.0514 |
Reading the sea-level chart understates the humidity ratio by 2.97 g/kg and the dew point by 1.0 K. The wet bulb equation starts from the saturation humidity ratio at the wet bulb temperature and subtracts a term for the depression. Lower pressure raises that saturation humidity ratio, so the same dry bulb and wet bulb pair means more moisture.
3) Room air defined by dry bulb and RH. At 24 °C / 50 % the vapour partial pressure is the same at any altitude, so the dew point is the same 12.9 °C. Humidity ratio, W = 0.621945 × pw / (p − pw), has barometric pressure in the denominator: 9.30 g/kg at sea level against 11.18 g/kg at the site. Enthalpy rises from 47.81 to 52.59 kJ/kg. A condensation check that only compares dew points is fine with sea level values, but latent load or humidifier sizing from a humidity ratio difference needs the site value.
4) Supply airflow. The dry air mass flow needed to carry 30 kW sensible over 10 K is ṁ = 30 / (1.0268 × 10) = 2.9217 kg/s, practically the same as at sea level (2.9317 kg/s). The volume is what changes. Supply air at 14 °C has a specific volume of 0.8256 m³/kg at sea level and 0.9923 m³/kg at the site, so the airflow goes from 8,714 CMH to 10,437 CMH, 19.8 % more. That is almost exactly the pressure ratio, 1.198.
5) Outdoor air coil. 3,000 CMH of outdoor air is 0.9542 kg/s of dry air at sea level and 0.7926 kg/s at the site. The coil leaving state at 14 °C / 90 % has an enthalpy of 36.72 kJ/kg at sea level and 41.29 kJ/kg at the site.
| 3,000 CMH outdoor air | Sea-level chart | Actual at 1,500 m |
|---|---|---|
| Enthalpy difference (kJ/kg) | 20.35 | 23.38 |
| Total coil load (kW) | 19.4 | 18.5 |
| Sensible part (kW) | 15.7 | 13.1 |
| Latent part (kW) | 3.8 | 5.5 |
| Condensate (kg/h) | 5.35 | 7.78 |
Sensible heat uses cp = 1.006 + 1.86 WO, and latent is the total minus sensible. The thinner air cuts the mass flow by 16.9 %, but the enthalpy difference grows by 14.9 %, so the total load lands close to the sea-level figure: 19.4 kW against 18.5 kW. The condensate, however, is 45 % higher.
6) Across altitudes. The same inputs with only the elevation changed (outdoor from 30 °C dry bulb / 20 °C wet bulb, room at 24 °C / 50 %).
| Elevation | Pressure (kPa) | Outdoor W (g/kg) | Room W (g/kg) | Supply specific volume (m³/kg) | Supply airflow (CMH) | OA coil condensate (kg/h) |
|---|---|---|---|---|---|---|
| 0 m | 101.33 | 10.52 | 9.30 | 0.826 | 8,714 | 5.35 |
| 500 m | 95.46 | 11.44 | 9.88 | 0.877 | 9,248 | 6.20 |
| 1,000 m | 89.87 | 12.42 | 10.50 | 0.933 | 9,821 | 7.00 |
| 1,500 m | 84.56 | 13.49 | 11.18 | 0.992 | 10,437 | 7.78 |
| 2,000 m | 79.50 | 14.64 | 11.90 | 1.057 | 11,100 | 8.51 |
| 2,500 m | 74.68 | 15.89 | 12.68 | 1.126 | 11,813 | 9.21 |
What the numbers mean in practice
At 1,500 m the biggest difference is airflow. Keep a fan sized for the sea-level 8,714 CMH and it moves the same volume but less mass, so it covers 25.0 kW of sensible load instead of 30 kW. Unless the supply temperature drops further, the room will not hold its set point. The sound approach at altitude is to work the loads out as mass flow, convert to volume with the site specific volume, and select fans and coils on that volume.
The second difference is moisture. A sling psychrometer reading plotted on a sea-level chart understates both humidity ratio and dew point. Here the dew point is off by 1.0 K, which is enough to flip a condensation call on outdoor air ducts or cold piping if you were working to a 1 to 2 K dew point margin. A sensor that measures RH directly needs no altitude correction, but pressure comes into play as soon as you convert its reading to humidity ratio.
The third is the make-up of the coil load. Even with a similar total, the latent share is larger, so recheck condensate drainage and dehumidification capacity. If the coil manufacturer's selection software has an altitude or barometric pressure field, always fill it in with the site value.
Some things genuinely do not change. The dew point of air at a given dry bulb and RH, and an indoor condition specified only as temperature and RH, are independent of altitude. Judging condensation by comparing a surface temperature to the room dew point works exactly as at sea level.
Beyond the calculation
The standard atmosphere equation gives the average pressure for an elevation. Actual barometric pressure moves by a few kPa with the weather, so if you have a barometer reading on site, use it. The calculators on this site accept a pressure in kPa directly as well as an elevation.
At a fixed speed a fan delivers the same volume, while its pressure and shaft power fall in proportion to air density (the fan laws). If a catalogue rates performance at standard air, apply the density correction before reading it. Combustion equipment such as boilers and burners sees less oxygen per unit volume, which affects output and combustion setup, so check the manufacturer's high-altitude data separately. Cooling towers and evaporative coolers depend on wet bulb and air mass flow too, so they need the same correction.
Common mistakes
- Plotting wet bulb readings on a sea-level chart. At 1,500 m this understates the humidity ratio by 22 % (10.52 vs 13.49 g/kg).
- Converting mass flow to airflow with the sea-level specific volume. You get 8,714 CMH when 10,437 CMH is needed.
- Keeping the 1.2 in the shortcut q = 1.2 × 1.005 × airflow (m³/s) × ΔT. 1.2 kg/m³ is the density of room temperature air near sea level. At altitude, recalculate from the site specific volume.
- Trying to correct RH and dew point as well. The dew point at a given dry bulb and RH does not depend on altitude. What needs correcting is humidity ratio, enthalpy, specific volume, and anything read from a wet bulb.
- Assuming similar coil load means similar condensate. Here the condensate goes from 5.35 to 7.78 kg/h.
Try this calculation on the site
The chart link sets the pressure to the 1,500 m value and plots the outdoor, coil leaving and room points with a coil process card for 3,000 CMH of outdoor air. Switch the pressure back to sea level to compare with the sea-level column above. To get humidity ratio straight from dry bulb and wet bulb, use the humidity calculator at 1,500 m. For the full coil selection workflow see Cooling coil selection and reheat, for treating outdoor air on its own see DOAS outdoor air and latent load, and for plotting see How to read a psychrometric chart.
References
- ASHRAE Handbook Fundamentals 2017 (SI), chapter 1 Psychrometrics: the standard atmosphere relation between elevation and pressure (equation 3), the humidity ratio, enthalpy, specific volume and wet bulb equations, and saturation vapour pressure (Hyland-Wexler). The numbers here were computed with this site's engine, which implements those equations.
- In the same chapter, humidity ratio W = 0.621945 pw/(p − pw) and specific volume v = 0.287042 (t + 273.15)(1 + 1.607858 W)/p contain barometric pressure directly. Relative humidity and dew point depend only on vapour partial pressure and saturation pressure.
- The density correction of fan performance (pressure and power proportional to density at fixed speed) is the general fan law.
- The 1,500 m elevation, 30 °C / 20 °C wb outdoor air, 24 °C / 50 % room, loads and airflows are example values. Real outdoor design conditions come from local weather data.