Kitchen makeup air heating and cooling load: where should the air replacing the hood exhaust be treated

A kitchen hood exhausts a lot of air, and the same amount of outdoor air has to come back in somewhere. Supply it through a makeup air unit and that unit has to heat or cool it; leave it out and the same outdoor air leaks in through the dining room and doors, and the dining room HVAC pays for it. We put numbers on how far to cool it in summer, how warm to supply it in winter, and how the dining room load changes with the makeup ratio.

10 20 30 40 50 60 70 80 90 0 5 10 15 20 25 30 35 40 0 5 10 15 20 25 °C g/kg O B C R H 30 40 50 60 70 80 90 10 15 20 25 30 35 0 5 10 15 20 25 °C g/kg O B C R H
Kitchen makeup air treatment. Bold = summer outdoor O cooled and dehumidified to C at the dining room humidity ratio, fine dots = O cooled sensibly to B at 26 °C (humidity ratio unchanged), heating line = winter outdoor air (−10 °C, off the left edge, so drawn from the chart edge) heated to H at 18 °C.

Situation

Say a restaurant kitchen hood exhausts 10,000 CMH. To keep cooking odours out of the dining room the kitchen is held slightly negative: 85 % of the exhaust (8,500 CMH) is outdoor air supplied directly by a dedicated makeup air unit, and the remaining 15 % (1,500 CMH) is drawn from the dining room as transfer air. Three questions. In summer, what does the coil take if the makeup air is left untreated, cooled sensibly, or dried down to dining room level? In winter, how warm should it be supplied and how much heat does that take? And if the makeup ratio is cut, how much load moves to the dining room? The conditions are illustrative; real exhaust rates and design weather come from the cooking equipment, the hood type and local data.

Given conditions

ItemValue
Hood exhaust10,000 CMH. Makeup air 85 % = 8,500 CMH, transfer air from the dining room 1,500 CMH
Summer outdoor ODry-bulb 33 °C, RH 60 % (humidity ratio 19.11 g/kg, dew point 24.2 °C, enthalpy 82.2 kJ/kg, specific volume 0.8939 m³/kg)
Dining room R (summer)Dry-bulb 26 °C, RH 50 % (humidity ratio 10.50 g/kg, enthalpy 52.9 kJ/kg)
Winter outdoor WDry-bulb −10 °C, RH 50 % (humidity ratio 0.80 g/kg, enthalpy −8.08 kJ/kg, specific volume 0.7464 m³/kg). Dining room at 22 °C
Airflow basisAll CMH figures are volumes at outdoor intake conditions, so volume ratios equal mass ratios
Pressure101.325 kPa (sea level)

Reading it on the chart

  1. Plot summer outdoor O (33 °C, 60 %) and the dining room R (26 °C, 50 %). A horizontal line left from O meets the saturation curve at the outdoor dew point, 24.2 °C.
  2. Sensible cooling B: move horizontally from O to 26 °C. If the coil surface stays above the 24.2 °C outdoor dew point (warm chilled water, for example), nothing condenses and the humidity ratio stays put, and the RH curves put B at about 90 %.
  3. Dehumidifying C: draw a horizontal line left from R until it meets the 95 % RH curve. The line from O to C is a cooling and dehumidifying coil.
  4. Winter: outdoor W (−10 °C) is off the left edge of most charts. Draw a horizontal line at 0.80 g/kg out to 18 °C; that is the heated state H.

Step-by-step calculation

1) Summer makeup air mass flow. At the outdoor specific volume of 0.8939 m³/kg, ṁ = 8,500 / 3600 / 0.8939 = 2.6413 kg/s.

2) A: untreated. No coil load. The kitchen receives 33 °C air at 82.2 kJ/kg, and with the cooking heat on top it runs far hotter than the dining room.

3) B: sensible cooling to 26 °C. B has an enthalpy of 74.88 kJ/kg. Load = 2.6413 × (82.17 − 74.88) = 19.3 kW. Nothing condenses (assuming the coil surface stays above the dew point; an ordinary chilled-water coil runs colder and dries the air a little), but the RH climbs to 89.8 %.

4) C: dried to the dining room humidity ratio. C is at 10.50 g/kg, 15.6 °C dry-bulb and 42.23 kJ/kg. Load = 2.6413 × (82.17 − 42.23) = 105.5 kW, with 81.9 kg of condensate per hour (the enthalpy the condensate carries off is ignored). That is 5.5 times the sensible-only load.

5) Winter heating. At the winter specific volume of 0.7464 m³/kg the same 8,500 CMH is 3.1632 kg/s, 19.8 % more mass than in summer. Heating at constant humidity ratio to 18 °C gives H at 20.13 kJ/kg, so the heating load is 3.1632 × (20.13 − (−8.08)) = 89.2 kW.

Winter supply temperatureHeating (kW)Supply RH (%)
10 °C63.710.6
15 °C79.77.6
18 °C89.26.3

6) Transfer air from the dining room. If 1,500 CMH moves from the dining room into the kitchen, the dining room has to bring in the same amount of outdoor air and condition it. In summer that costs hO − hR = 29.25 kJ per kg of air; in winter, heating it to 22 °C costs 32.24 kJ/kg. For 1,500 CMH that is 13.6 kW of cooling in summer and 18.0 kW of heating in winter.

7) Changing the makeup ratio. Holding the treatment fixed (summer B, sensible cooling; winter supply at 18 °C) and changing only the ratio:

Makeup ratioMakeup air (CMH)Transfer from dining (CMH)Summer makeup coil (kW)Summer extra dining cooling (kW)Winter makeup heating (kW)Winter extra dining heating (kW)
0 %010,0000.090.90.0120.0
50 %5,0005,00011.345.452.560.0
70 %7,0003,00015.927.373.536.0
85 %8,5001,50019.313.689.218.0
100 %10,000022.70.0105.00.0

Interpreting the result

With no makeup air (0 %), all 10,000 CMH of exhaust is replaced through the dining room, which then has to find an extra 90.9 kW of cooling in summer and 120.0 kW of heating in winter. Both are large: in summer the outdoor moisture has to come down to dining room conditions too, and in winter −10 °C air has to be warmed 32 K to 22 °C. Dining room units are rarely sized for that much outdoor air, so the room ends up hot and sticky, with drafts at the door gaps and doors that are hard to open. That is why kitchen exhaust normally gets its own makeup air, with only enough transfer air from the dining room to keep the kitchen negative.

How far to treat the air in summer depends on what the kitchen needs. B (sensible to 26 °C) costs 19.3 kW but delivers muggy air at 90 % RH. C (dried to dining room level) costs 105.5 kW, 5.5 times as much, and over half of it (about 58 kW) is latent: wringing out moisture. If most of the makeup air goes straight up the hood, expensive dry air is simply being thrown away, so spot cooling at the cook line or B-level treatment is often the realistic choice. If the kitchen is wide open to the dining room, treatment closer to C is needed to hold the dining room humidity.

In winter the supply temperature translates directly into heating. Going from 10 °C to 18 °C adds 25.5 kW. Too cold and the cooks complain of cold drafts; too warm and you are heating air that leaves through the hood moments later. The supply RH is only 6.3 %, very dry, but kitchens produce plenty of cooking vapour and are usually not humidified.

What the calculation leaves out

The hood exhaust rate is set by the cooking equipment and the hood type; this article does not calculate it. Makeup air blown hard just in front of the hood can disturb the hood's capture of smoke and heat, so discharge location and velocity should be settled with the hood manufacturer's data.

Heating sub-zero outdoor air with a hot-water coil risks freezing the coil (direct gas-fired makeup air heaters, which have no coil, are also common for kitchens). Use a preheat coil, freeze-protection temperature monitoring and interlocked dampers ahead of the coil. The largest saving is usually interlocking exhaust and makeup air so both turn down or off when the cooking stops. This looks only at one design outdoor condition; annual energy needs hourly weather data and the opening hours.

Common mistakes

  • Designing the exhaust and forgetting the makeup air. If all 10,000 CMH comes in through the dining room, the dining room cooling has to cover another 90.9 kW.
  • Assuming sensible cooling makes the air comfortable. Cooled to 26 °C it is still at 90 % RH. A horizontal move on the chart leaves the humidity ratio unchanged.
  • Treating equal volumes as equal mass. The same 8,500 CMH of −10 °C outdoor air has 19.8 % more mass than at 33 °C. Size the heating with the winter specific volume.
  • Setting makeup air above 100 % of the exhaust. The kitchen goes positive and pushes odours and heat into the dining room. Taking 15 % from the dining room here is what keeps the kitchen negative.
  • Forgetting the heating coil can freeze. −10 °C outdoor air straight onto a hot-water coil can freeze it when the unit is off or the water flow is low.

Try this calculation on the site

Open the summer makeup air treatment on the chart

Open the winter makeup air heating on the chart

The summer link plots the outdoor, sensible-cooled, dehumidified and dining room points with process cards from outdoor to both coil leaving states; the winter link plots the heating from outdoor to 18 °C, so you can check the loads. For coil leaving conditions see the cooling coil calculator, for free cooling see the economizer calculator, for a unit that treats only outdoor air see DOAS outdoor air and latent load, and for plotting see How to read a psychrometric chart.

References

  • ASHRAE Handbook Fundamentals 2017 (SI), chapter 1 Psychrometrics: humidity ratio, enthalpy, specific volume and saturation vapour pressure (Hyland-Wexler). The psychrometric numbers here were computed with this site's engine, which implements those equations at 101.325 kPa.
  • The link between kitchen exhaust and makeup air, and the effect of makeup air discharge on hood capture, are general principles covered in the Kitchen Ventilation part of ASHRAE Handbook HVAC Applications. This article does not quote chapter numbers or specific design values from it.
  • The 10,000 CMH exhaust, 85 % makeup ratio, summer outdoor 33 °C / 60 %, dining room 26 °C / 50 %, winter outdoor −10 °C / 50 % and the supply temperatures are example values. Real values come from the codes that apply to the premises and local design weather data.